Abstract
A new local control strategy with non-linear optimal controllers for a multimachine system is presented. Non-linear Field Voltage Controllers (NFVC) are designed with the use of the feedback linearization approach to adjust generator state variables to external reference signals resulting from optimal power flow calculation [Pi,Qi, Vti] in the stabilized power system. A non-linear control law has been derived for the three-dimensional [δ,ω,E′q] one-axis model of a generator. The local control strategy has been verified for the New England 39 bus system. An extensive simulation study shows robustness of the non-linear controllers and better performance than PSS-based classical controllers.
| Original language | English |
|---|---|
| Pages (from-to) | 341-354 |
| Number of pages | 14 |
| Journal | Optimal Control Applications and Methods |
| Volume | 18 |
| Issue number | 5 |
| DOIs | |
| Publication status | Published - 1997 |
| Externally published | Yes |
Keywords
- Feedback linearization
- Non-linear control systems
- Power system control
Fingerprint
Dive into the research topics of 'Stabilizing a multimachine system via non-linear voltage controller with the use of a local control strategy'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver