Skip to main navigation Skip to search Skip to main content

Stabilizing a multimachine system via non-linear voltage controller with the use of a local control strategy

Research output: Contribution to journalArticlepeer-review

Abstract

A new local control strategy with non-linear optimal controllers for a multimachine system is presented. Non-linear Field Voltage Controllers (NFVC) are designed with the use of the feedback linearization approach to adjust generator state variables to external reference signals resulting from optimal power flow calculation [Pi,Qi, Vti] in the stabilized power system. A non-linear control law has been derived for the three-dimensional [δ,ω,E′q] one-axis model of a generator. The local control strategy has been verified for the New England 39 bus system. An extensive simulation study shows robustness of the non-linear controllers and better performance than PSS-based classical controllers.

Original languageEnglish
Pages (from-to)341-354
Number of pages14
JournalOptimal Control Applications and Methods
Volume18
Issue number5
DOIs
Publication statusPublished - 1997
Externally publishedYes

Keywords

  • Feedback linearization
  • Non-linear control systems
  • Power system control

Fingerprint

Dive into the research topics of 'Stabilizing a multimachine system via non-linear voltage controller with the use of a local control strategy'. Together they form a unique fingerprint.